- Description
- Attributes
- Documents
- Nominal voltage AC: max. 240 V, 50 / 60 Hz
- Nominal voltage DC: max. 240 V
- Rated current: 4 x 6 A at 40 °C ambient temperature
- Decoupling inductor: 4 x 20 mH / 6 A (series choke)
- Coupling capacity: 0.5 µF
- Series resistance: 40 Ohm
- Maximum pulse voltage 1.2/50 µs: 4400 volts
- High voltage (HV) - Input: Fischer HV socket D105A039
- Input / Output coupling network: lab jacks
- Interface: serial, RS232
- Supply voltage input: 100-240 V / 47-63 Hz / 80 VA plug-in power filter on the back
- Earth connection: additionally via socket on the front and rear side
- Operating temperature: 0 - 40°C
- Rel. humidity 0 - 60 %
- Weight: approx. 14 kg
- Dimensions (H x W x D): 19” housing (3 RU)
The coupling network can be used for EMC tests according to the IEC 61000-4-5 (Surge) standard. The interference pulses of the surge generator are coupled to the EUT's connecting lines. The coupling paths (line to line or line to earth) can be selected by means of switches. The coupling network can be remotely controlled from a PC via an RS232 interface in conjunction with the CWG 2500/1500 Surge Generator. This allows the selection of the coupling paths to be automated. The CWG 1528 is suitable for operation with the CWG 2500 / 1500 surge generators from Schlöder.
Scope of Delivery:
HV cable with 0.85 m length for connection to the Surge Generators: CWG 1500 / CWG 2500
Brand: Schloeder
AC Voltage: 240 V
Current Rating: 6 A
DC Voltage: 240 V
Resistance: 40 Ω
Series: CWG Series
£
£